1 of 4 Copyright © 1999 U 362 -06/99
The tekmar Mixing Control 362 has a Liquid Crystal Display (LCD) and four push
buttons (
Menu
,
Item
, , ) which are used to view and adjust the settings.
Menu
All of the items displayed by the control are organized into various menus. These menus
are listed on the left hand side of the display (Menu Field). To select a menu, use the
Menu
button. By pressing and releasing the
Menu
button, the display will advance to the
next available menu. Once a menu is selected, there will be a group of items that can
be viewed within that menu.
Item
The abbreviated name of the selected item will be displayed in the item field of the display.
To view the next available item, press and release the
Item
button. Once you have
reached the last available item in a menu, pressing and releasing the
Item
button will
return the display to the first item in the selected menu.
Adjust
To make an adjustment to a setting in the control, begin by selecting the appropriate
menu using the
Menu
button. Then select the desired item using the
Item
button. Finally,
use the and/or button to make the adjustment.
- User Brochure
U 362
06/99
Mixing Control 362
User Interface
The Mixing Control 362 is a microprocessor base control designed to operate either a variable speed injection
pump or a floating action mixing valve in order to provide a mixed supply water temperature to a hydronic
system. The control is designed to operate in two distinct modes. Mode 1 allows for the control to provide a
reset mixed supply water temperature to maximize the comfort and efficiency of a hydronic heating system.
Multiple zone temperature control is achieved by using either thermostats or tekmar Zone Controls. Mode 2
allows for control of a snow melting slab. Standard features include boiler protection (when a boiler sensor
is installed), pump exercising, and digital temperature readouts.
Access Level(s) The tekmar Mixing Control 362 has four access levels which are LTD (limited), USER, INST (Installer), and ADV
(advanced). This brochure only covers the LTD (Limited) and USER levels. Only qualified service people should adjust the INST
(Installer) and ADV (advanced) access levels.
Additional information can be gained by observing the Status and Pointers fields of the LCD. The status field will indicate which of the
control’s outputs are currently active. Most symbols in the status field are only visible when the View Menu is selected.
Mix Demand
WWSD
Minimum
Maximum
Melting
Idling
Menu
Item
Number Field
Displays the current value
of the selected item
{
Buttons
Selects Menu,
Items and adjusts
settings
Misc
°
F
°
C
Ovr
View
Adjust
Schd
hr
Monitor
Open
Close
1
%
Menu Field
Displays the
current menu
Status Field
Displays the
current status of
the control’s
inputs, outputs
and operation
Item Field
Displays an abbreviated
name of the selected item
UnOcc
!
sec
min
!
1
%
Open / Close
Displays when the actuator is
opening or closing the valve.
Mixing Device Output Scale
Shows output of injection pump
or mixing valve. Arrows show
whether the output is increasing
or decreasing.
Burner
Displays when the boiler relay
is turned on.
Pump
Displays when mixing pump is
operating.
Boost
Displays when the control is in
boost after setback.
UnOccupied
Displays when control is in
unoccupied mode.
Occupied
Displays when the control is in
occupied mode.
Override
Displays when the control is in
override mode.
Warning
Displays when an error exists
or a limit has been reached.
Lock - Unlock
Displays whether access
levels are locked or unlocked.
°F, °C, sec, min, hr,
Units of measurement.
Pointer
Displays control operation as
indicated by text.
UnOcc
Ovr
Close
Open
°
F,
°
C, sec,
min, hr
Occ
R
Menu
Item
LR 58223
NRTL/C
Mixing Control 362
Floating Action / Variable Speed
Mix Demand
WWSD
Minimum
Maximum
Melting
Idling
°
F
Vie
Ope
Occ
Page view 0
1 2 3 4

Summary of Contents

Page 1 - - User Brochure

1 of 4 Copyright © 1999 U 362 -06/99The tekmar Mixing Control 362 has a Liquid Crystal Display (LCD) and four pushbuttons (Menu, Item, , ) which are

Page 2

Copyright © 1999 U 362 -06/99 2 of 4Current outdoor air temperature as measured by the outdoorsensor. This is also the default display for the control

Page 3 - ItemMenu

3 of 4 Copyright © 1999 U 362 -06/99Room Temperature Unit (RTU) 062, 063A single RTU can be connected to the Mixing Control 362 in order to provide th

Page 4 - Remote Display Module (RDM)

Remote Display Module (RDM)An optional Remote Display Module can be connected up to the 362 if an RTU is not used. All items displayed on the 362 menu

Comments to this Manuals