Tekmar 402 House Control Installation User Manual

Browse online or download User Manual for Sensors Tekmar 402 House Control Installation. tekmar 402 House Control Installation User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 32
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
1 of 32 © 2010 D 402 - 09/10
tekmarNet
®
2 House Control 402
D 402
09/10
HVAC Systems
Replaces: 01/10
Installation & Operation Manual
Menu
House Control 402
Item
VIEW
Boil Exp Boil System
Zones
1 2 3 4
Calls
Pumps
Benefi ts
Energy efficiency through Outdoor Temperature
Reset with Indoor Feedback
Indoor Feedback minimizes the water temperature
(increasing energy savings), and the efficiency of
your mechanical equipment through integrated
tekmarNet
®
Thermostats
Zone Synchronization reduces equipment cycling
Auto Differential - Reduces boiler cycling
Compact enclosure for flexible installation
Simple zone expansion using Wiring Centers
The House Control 402 is designed to operate as part of a
complete hydronic heating system with tekmarNet
®
2 (tN2)
thermostats. It can provide operation of two outdoor reset
water temperatures such as radiant floor heating on the first
temperature and baseboard or fan coil heating on the second
temperature. In addition the control has Domestic Hot Water
and Setpoint capabilities. It is easy to add more zones, add
schedules or other convenient accessories through the use
of the tekmarNet
®
4 (tN4) Expansion terminals.
Features
Single on-off, two-stage or modulating boiler
Boiler outdoor reset temperature
Mixing outdoor reset temperature
Domestic Hot Water tank operation
Setpoint operation
Mix with variable speed injection, floating action,
or proportional 0-10 V (dc), proportional 4-20 mA
For use with tekmarNet
®
2 Thermostats
Four 24 V (ac) powered zone valve outputs
Expand to 24 zones per temperature using
tekmarNet
®
4 expansion ports
CSA C US Certified for use in USA and Canada
Introduction
Page view 0
1 2 3 4 5 6 ... 31 32

Summary of Contents

Page 1 - Introduction

1 of 32 © 2010 D 402 - 09/10tekmarNet®2 House Control 402D 40209/10HVAC SystemsReplaces: 01/10Installation & Operation ManualMenuHouse Control 4

Page 2 - Installation

© 2010 D 402 - 09/10 10 of 32Step 8 The DHW pump turns on for 10 seconds.Step 9 The boiler system pump turns on for 10 seconds.Step 10 During the boil

Page 3 - Physical Dimensions

11 of 32 © 2010 D 402 - 09/10ApplicationsMixBoilDHWVariable Speed(P4)(P1)(P3)(P2)115 V (ac)NLGto pump groundsNLBack of House Control 402Strip wires1

Page 4 - Load (VA)

© 2010 D 402 - 09/10 12 of 32Description: The House Control 402 operates a modulating boiler with indirect Domestic Hot Water. Mixing is performed wit

Page 5 - 12-18 AWG

13 of 32 © 2010 D 402 - 09/10CallsCALLSDisplays any call for heat the control is receiving. PumpsPUMPSDisplays any pump currently operating.Zones1 2

Page 6 - © 2010 D 402 - 09/10 6 of 32

© 2010 D 402 - 09/10 14 of 32Navigating The DisplayMenu Button ---------------------------------------------------------------------------------------

Page 7 - Sensor Wiring

15 of 32 © 2010 D 402 - 09/10Item Field Range DescriptionVIEWZonesCallsPumps-76 to 149°F(-60.0 to 65.0°C)OUTDOOR SECTION B, CCurrent outdoor air te

Page 8

© 2010 D 402 - 09/10 16 of 32Item Field RangeAccessDescription Set toADJUST-60 to 45°F(-51.0 to 7.0°C)Default = 10°F(-12.0°C)InstallerOUTDOOR DESIGN

Page 9 - Testing the Control Wiring

17 of 32 © 2010 D 402 - 09/10Item Field RangeAccessDescription Set toVIEW70 to 200°F(21.0 to 93.5°C)Default = 180°F (82.0°C)InstallerBOILER DESIGN

Page 10 - Max Heat

© 2010 D 402 - 09/10 18 of 32Item Field RangeAccessDescription Set toADJUST40 to 100°F(4.5 to 38.0°C)Default = 70°F(21.0°C)InstallerUserWWSD OCCUPIED

Page 11 - Applications

19 of 32 © 2010 D 402 - 09/10Item FieldRangeDescriptionMONITOR-76 to 149°F(-60.0 to 65.0°C)OUTDOOR HIGHRecords the highest outdoor temperature since

Page 12 - House Control 402

© 2010 D 402 - 09/10 2 of 32 Table of Contents Getting Started Caution Installation ...

Page 13 - User Interface

© 2010 D 402 - 09/10 20 of 32Item FieldRangeDescriptionOn or OffDefault = OffUSER TEST TESTINGBegins the test routine which tests the main control’s

Page 14 - Programming and Settings

21 of 32 © 2010 D 402 - 09/10Sequence of Operation tekmarNet® System Section AtekmarNet® is a family of products that use communication to operate t

Page 15 - VIEW MENU

© 2010 D 402 - 09/10 22 of 32Mixing Device Type ----------------------------------------------------------------------------------- ------------------

Page 16 - ADJUST MENU

23 of 32 © 2010 D 402 - 09/10 Domestic Hot Water Tank Operation Section DA DHW Call is required in order for the control to provide heat to a DHW ta

Page 17

© 2010 D 402 - 09/10 24 of 32DHW MODE 3 - DHW in Primary / Secondary no PriorityWhen a DHW Call is present, the DHW pump and the boiler system pump is

Page 18

25 of 32 © 2010 D 402 - 09/10 Setpoint Operation Section EA Setpoint Call is required in order for the control to provide heat to a setpoint load, s

Page 19 - MONITOR MENU

© 2010 D 402 - 09/10 26 of 32Boiler Maximum -------------------------------- --------------------------------The 402 will operate the boiler so that t

Page 20 - TOOLBOX MENU

27 of 32 © 2010 D 402 - 09/10Auto Differential -------------------------------- --------------------------------Both on-off and modulating boilers a

Page 21 - Sequence of Operation

© 2010 D 402 - 09/10 28 of 32The “$aving” icon is displayed when energy is being saved. The following features reduce energy consumption.Network Sched

Page 22 - Boil Exp

29 of 32 © 2010 D 402 - 09/10Error Message DescriptionOUTDOOR SENSOR OPEN CIRCUITDue to an open circuit (disconnected or broken wire), the control f

Page 23 - Section D

3 of 32 © 2010 D 402 - 09/10Materials Required ----------------------------------------------------------------------------------- -----------------

Page 24

© 2010 D 402 - 09/10 30 of 32 Error Messages (3 of 3) Error Message DescriptionMIX DEVICE LOST (1:01 TO 1:24)Each tekmarNet® device (thermostat, setpo

Page 25 - Setp

31 of 32 © 2010 D 402 - 09/10Symptom Look For...Corrective ActionNo central heatingBurner symbol on LCDIf the burner symbol is on the LCD, there is

Page 26

Product design, software and literature are Copyright © 2010 by:tekmar Control Systems Ltd. and tekmar Control Systems, Inc.32 of 32All specifications

Page 27 - Section H

© 2010 D 402 - 09/10 4 of 32The control requires an external transformer. A tekmar Transformer 009 (or 009K which includes a 4”x 4” electrical box) ca

Page 28 - Troubleshooting

5 of 32 © 2010 D 402 - 09/10DHW PumpMix System PumpPower Source (L,N)V. S. PumpBoil Sys PumpBoil System PumpMix System PumpDHW PumpVariab leSpeed Pu

Page 29 - Error Messages (2 of 3)

© 2010 D 402 - 09/10 6 of 32External Power SupplyIt is strongly recommended that a transformer with an in-line fuse be used in order to protect the tr

Page 30 - Error Messages (3 of 3)

7 of 32 © 2010 D 402 - 09/10RCLNComOpenCloseExpansiontN4 BoilCtN4ModulatingBoiler—+ExpansiontN4 MixCtN421WCWCMenuHouse Control 402Item+Mix ComBoil O

Page 31 - Job Record

© 2010 D 402 - 09/10 8 of 32Connect 18 AWG or similar wire to the two terminals provided in the enclosure and run the wires from the 070 to the contro

Page 32 - Technical Data

9 of 32 © 2010 D 402 - 09/10A good quality test meter capable of measuring up to 5,000 kΩ (1 kΩ = 1000 Ω) is required to measure the sensor resistan