Tekmar 365 Mixing Control User Manual

Browse online or download User Manual for Sensors Tekmar 365 Mixing Control. tekmar 365 Mixing Control User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 16
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Copyright © D 365 - 06/001 of 16
Outdoor Reset Strategy. . pg. 2
Variable Speed Pump . . . pg. 3
Sequence of Operation . . pg. 5
Installation . . . . . . . . . . . . pg. 7
Settings . . . . . . . . . . . . . . . pg. 11
N
0.4
2.0
3.6
Heating Curve
Dem
L
12 3456
Pmp
Mixing Control 365
Dem Pmp
89
150°F
100 200
Max./Setpoint
Minimum
Boiler Return
Motor Speed /
Pump Response
Test
Boiler
Occupied
35
(2)
105
(41)
70°F
(21°C)
Unoccupied
35
(2)
105
(41)
70°F
(21°C)
H1073
OR
Variable Speed and 4-20 mA
130 sec.
30 230Off
100°F
150
60
7
Var.
Pmp
90
70
50
30
10
Power
WWSD
UnOcc.
Switch
Min.
Return
Boiler
Heat
Demand
Max. or
Setpoint
Pump
Setpoint
Permanent Heat Demand
Indoor Sensor
Zone Control
Boiler on when 25% open
Reset
Boiler on when 10% open
External Heat Demand
OR
M
Heat
Power
System
Use Nº 20 AWG or larger copper conductors rated for at least 75°C and 300V.
%
of full
output
R
R
LR 58223
E150539
Listed
5T62
Input:
Heat Demand
signal.
Optional
120Vac
Power Supply
Output: Turn on
system pump
Output: Control
variable speed pump
Output:
4-20mA device
Output:
Turn on boiler
Input: Return
Sensor 071.
Optional
Input:
Unoccupied
signal (030
Timer)
Optional
Input: Indoor
Sensor 074
Optional
Input: 2k RTU
Optional
Input: Supply Universal
Sensor 071.
Included
Input: Outdoor
Sensor 070
Included
Manufactured
in Canada by
Date
S/N
2093
1234567
Power: 120V 50/60Hz 300VA
System pump: 120Vac 12A 1/3 hp, pilot duty 480VA 4A
Var pump: 120V 50/60Hz 2.2A 1/6 hp, internally fused
Relay: 120Vac 10A 1/4 hp, pilot duty 240VA 2A
Enclosed Energy Management Equipment
13 14
Sen
RTU
2K10K
12 15
Sen
SenSw
UnO
16 17
Sen
Sup Out
Do not apply power here
Sen
18 19
Com
Sen
Ret
10 11
4-20
1000 max
+
Com Com
1
2
3 4
- Data Brochure
Mixing Control 365
D 365
06/00
R
R
R
R
LR 58233
E150539
Mixing Control 365
Occupied
35
(2
)
105
(41)
70°F
(21°C)
Unoccupied
35
(2
)
105
(41)
70°F
(21°C)
Variable Speed and 4-20 mA
90
70
50
30
10
Power
WWSD
UnOcc.
Switch
Min.
Return
Boiler
Heat
Demand
Max. or
Setpoint
Pump
%
of full
output
The tekmar Mixing Control 365 is a microprocessor-based control with a 120 Vac output for operating
a variable speed injection pump. A 4-20mA output is available for operating devices such as a 4-
20mA actuating motor, modulating gas valve, a mixing valve combination, or for operating a 4-20mA
motor drive for larger variable speed pumps. The variable speed pump or mixing valve regulates the
supply water temperature to a heating system based on the outdoor air temperature, and optionally,
the indoor air temperature. The system is shut down when there is no Heat Demand signal or when
the outdoor temperature is warm enough so that the system no longer requires heat (WWSD).
Testing . . . . . . . . . . . . pg. 13
Error Messages . . . . . pg. 15
Technical Data . . . . . . pg. 16
Limited Warranty . . . . pg. 16
Variable Speed
and 4-20 mA
operating level
Terminal Plugs:
Power and out-
put connections
System
Pump
is on
Unoccupied
temperature
setting
Occupied
temperature
setting
Operating Mode
selector
switches
Terminal Plug:
Sensor and
timer input
Test button and
LED to test main
control functions
Motor Speed
Minimum
Boiler Return
Maximum
Supply
/Setpoint
Heating Curve
Control is
maintaining
Minimum Return
Control is
maintaining
Maximum Supply
System is
switched to
Unoccupied
System is in
Warm Weather
Shut Down
120Vac power
supply is on
Heating
is required
Boiler is on
Page view 0
1 2 3 4 5 6 ... 15 16

Summary of Contents

Page 1 - - Data Brochure

Copyright © D 365 - 06/001 of 16Outdoor Reset Strategy. . pg. 2Variable Speed Pump . . . pg. 3Sequence of Operation . . pg. 5Installation . . . . . .

Page 2 - Outdoor Reset Strategy

Copyright © D 365 - 06/00 10 of 16Test the outputsIf a System Pump circuit is connected to the Sys Pmp — Sys Pmp (5 and 6) terminals; make sure power

Page 3 - High Output

Copyright © D 365 - 06/0011 of 16Step Six Essential control settingsTo obtain the best operation from a reset control, it is important to me

Page 4 - Plumbing Arrangements

Copyright © D 365 - 06/00 12 of 16Heat Demand switchWhen the heating system uses zone valve end switches or some other means of delivering an external

Page 5 - Sequence of Operation

Copyright © D 365 - 06/0013 of 16Indicator lightsThere are fourteen LEDs on the front of the control that will aid in testing and troubleshooting. Du

Page 6 - Occupied/Unoccupied dial:

Copyright © D 365 - 06/00 14 of 169070503010PowerWWSDUnOcc.SwitchMin.ReturnBoilerHeatDemandMax. orSetpointPump% of fulloutputTest9070503010PowerWWSDUn

Page 7 - Installation

Copyright © D 365 - 06/0015 of 16Step Nine Before you leave• Install the wiring cover over the wiring chamber and secure it to the base with the two

Page 8 - (Maximum 1/6 hp)

SpecificationsLimited Warranty and Product Return ProcedureLimited Warranty The liability of tekmar Control Systems Ltd. and tekmarControl Systems, In

Page 9 - type 365

Copyright © D 365 - 06/00 2 of 16Shifting the Heating Curve(a) Manually, at the control:The Occupied and Unoccupied dials on this control can shift th

Page 10 - Step Five Testing the wiring

Copyright © D 365 - 06/003 of 16Variable Speed PumpWhen using a variable speed pump, the injection of high tempera-ture water into the lower temperatu

Page 11 - Settings

Copyright © D 365 - 06/00 4 of 16tekmar has developed two significantly different ways of piping variable speed injection pumps for small commercial a

Page 12 - Pump Response

Copyright © D 365 - 06/005 of 16The control accepts a zone input signal from a tekmar 10K Zone Control which monitors theindoor temperature of all zon

Page 13 - Testing the Control Functions

Copyright © D 365 - 06/00 6 of 169070503010PowerWWSDUnOcc.SwitchMin.ReturnBoilerHeatDemandMax. orSetpointPump% of fulloutput9070503010PowerWWSDUnOcc.S

Page 14 - Step Eight Troubleshooting

Copyright © D 365 - 06/007 of 16CautionImproper installation and operation of this control could result in damage to equipment and possibly even perso

Page 15 - Error Messages

Copyright © D 365 - 06/00 8 of 16Rough-in wiring (continued)Option: A Universal Sensor 071 can be installed to provide Minimum Boiler Return protecti

Page 16 - Specifications

Copyright © D 365 - 06/009 of 16Powered input connectionsIf a 24Vac to 120Vac external heat demand signal is used, (zone valve end switches, etc.) con