Tekmar 371 House Control User Manual

Browse online or download User Manual for Sensors Tekmar 371 House Control. tekmar 371 House Control User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 20
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
1
D 371
07/96
The House Control 371 is a microprocessor-based control that provides individual tempera-
ture control for up to 5 zones. Each zone can be either connected to the boiler (hot water) loop
or to the mixing (warm water) loop. The supply water temperature to the zones is modulated
based on both the outdoor temperature and indoor temperature feedback from each of the
zones. This outdoor reset strategy reduces indoor temperature swings and increases system
efficiency. Other energy saving functions include a heating system Warm Weather Shut
Down (WWSD) and the ability to lower indoor temperatures for a night setback period. The
control has an Optimum Start / Stop function which automatically calculates when to bring
each zone out of night setback in order to ensure they are returned to their normal operating
temperatures as the setback period ends. The 371 allows integration of an indirect fired DHW
tank into the system. This helps provide faster DHW tank pick-up times and greater energy
savings. The control can also receive a setpoint demand on either the mixing loop or the boiler
loop for snow melting, hot tubs, or other loads.
Control Strategy ................... pg. 2 Testing the Control ...... pg. 16
Sequence of Operation ........ pg. 6 Error Messages ............ pg. 19
Installation ............................ pg. 10 Technical Data .............. pg. 20
Settings ................................. pg. 14 Limited Warranty .......... pg. 20
House Control 371
- Data Brochure
House Control 371
Five Zones, DHW, Boiler & Mixing
Power
WWSD
Minimum
Boiler
DHW
Demand
System
Pump 1
Boiler
Zone 3
24 hr. Timer
• Dial the desired duration
of the UnOccupied period.
• Press start button at the time of day
you want the UnOcc. period to begin.
Timer Active light turns on.
Start
UnOccupied
Duration
0 = always Occupied
24 = always UnOccupied
Maximum
Supply
Zone 2
Zone 4 /
Open
DHW
Pump
Zone 1 /
Cooling
90
70
50
30
10
%
of full
output
1
2
3
4
Setpoint
Demand
System
Pump 2
Zone 5 /
Close
5
70°F
(21°C)
40
(4)
100
(38)
UnOccupied
LR 58223
NRTL/C
Occupied
Optimum Start / Stop
UnOccupied
Timer Active
0
12 hrs.
24
618
R
House Control 371
Five Zones, DHW, Boiler & Mixing
Test
H1117 2
Made in Canada by
tekmar Control Systems Ltd.
N
234
P 1
5
Var.
Pmp
Power
L
Sys
12 13 14 15
130°F
Off 165
Min. Boiler
Supply
100
Power
Var. Pump
Relays
120 V 50/60 Hz 1500 VA
240 V 50/60 Hz 2.4 A 1/6 hp, fuse T2.5 A 250 V
120 V (ac) 3.2 A 1/4 hp, pilot duty 240 VA
Power
WWSD
Minimum
Boiler
DHW
Demand
System
Pump 1
Boiler
Zone 3
26 2725 28 29
30
Do not apply power here
3123 24
1-2
Com
1 3-5
Com
70°F
(21°C)
40
(4)
100
(38)
UnOccupied
678910 11
LR 58223
NRTL/C
R
Occupied
Optimum Start / Stop
UnOccupied
Timer Active
24 hr. Timer
0
12 hrs.
24
618
• Dial the desired duration of the
UnOccupied period.
• Press start button at the time of day
you want the UnOcc. period to begin.
Timer Active light turns on.
Start
0.2
2
3.6
1
3
Heating Curve
16 17 18
Com
Sen
RTU
1
RTU
2
Com
Sen
RTU
3
RTU
4
RTU
5
Com
Sen
UnO
Sw
Zo
In
Com
Sen
Boil
Sen
Sup
Sen
2220 21
Boiler Pmp
DHW
Setp
Dem Dem 2 3 4
Caution: Signal wiring must be rated at least 300V
Max. Supply / Setpnt
120
170°F
220
UnOccupied
Duration
0 = always Occupied
24 = always UnOccupied
Maximum
Supply
Zone 2
Zone 4 /
Open
DHW
Pump
Zone 1 /
Cool
90
70
50
30
10
%
of full
output
1
2
3
4
PRGM
S
TIME
AMPM
UNOCC
OVR
SMWTFT
1
2
LR 58233
E150539
70
70
70
70
Setpoint
Demand
System
Pump 2
Zone 5 /
Close
5
0.2
2
3.6
1
3
Boiler Heating
Curve
1
P 2
Sys
19
Out
Sen
DHW
5
Opn
Cls
M
70
Occ/UnOcc
Permitted
1,2
43
Occ. only
5 Setpnt
Boiler
Mixing
12345Zo
Off
Zone 1 Heat
Zone 1 Cool
Floating
DHW during UnOcc.
Var. Speed
Optimum Start
Thermal Motor
Zone
M
OR
Input
120 V (ac)
Power
Supply
Input
tekmar Zone
Control
Output
Mixed System
Pump
Output
Boiler
Input
Outdoor
Sensor
Included
Inputs
Universal
Sensors
Included
Input
tekmar RTUs or
Indoor Sensors
Input
Setpoint
Demand signal
Output
Var. Speed
Driven Pump
Output
Zone Valves or Zone
Pumps
Output
DHW
Pump
Input
tekmar
Timer
Output
Boiler System
Pump
Input
DHW
Demand signal
Output
Mixing Valve &
Actuating Motor
Output
Cooling
OR
Page view 0
1 2 3 4 5 6 ... 19 20

Summary of Contents

Page 1 - - Data Brochure

1D 37107/96The House Control 371 is a microprocessor-based control that provides individual tempera-ture control for up to 5 zones. Each zone can be e

Page 2 - Control Strategy

10Exercising ProcedureThe 371 first exercises the zone valves or pumps. If a zone valve or zone pump has not been operated in the past 3 days, the 371

Page 3 - DHW Priority

11DHW DemandIf a DHW demand is used, connect the switched wire from the DHW demand circuit toterminal DHW Dem (23). When 120 V (ac) relative to Neutra

Page 4 - PID Zone Temperature Control

12• If Zone 1 is used for heating (DIP switch set to Zone 1 Heat), connect the wire from the Zone 1 Pump or Valve to theCom 1-2 — 1 (25 and 26) termin

Page 5 - Zone Post Purge

13STEP FIVE TESTING THE WIRING Each terminal block must be unplugged from its header on the control before poweris applied for testing. Pull straight

Page 6 - Sequence of Operation

14BoilerIf a boiler is connected to the terminals Boiler — Boiler (20 and 21), make sure power to the boiler circuit is off and install a jumperbetwee

Page 7 - Max. Supply / Setpnt

15Boiler Minimum Supply Most boilers require a minimum operating temperature to prevent corrosion from flue gas conden

Page 8 - Cooling Control

16DIP Switch Settings Note Once the control is in operation, the control will not update any changes in theDIP switches unti

Page 9 - 24 hr. Timer

17During the test routine, the test sequence can be paused by pressing the Test button. The test sequence remains paused at that pointfor up to 5 minu

Page 10 - Installation

18System Pump 2• The relay contacts between Sys P2—Power L (1 and 4) are closed and the mixing system pump (P2)should be running.System Pump 1• The re

Page 11 - Output Connections

19STEP NINE BEFORE YOU LEAVE • Install the wiring cover over the wiring chamber and secure it to the base with the two screws provided. Place the fro

Page 12 - Floating

2Control StrategyOUTDOOR RESET In order to properly control a hot water heating system, the heat suppliedto the building must equal the heat lost by t

Page 13 - Test the Power Supply

20House Control 371 Five Zones, DHW, Boiler & MixingLiterature — A 000, A 371's, I 030, E 021, D 371, D 001, D 054, D 070, D 074Control — Mi

Page 14 - Settings

3Boiler Differential An on / off boiler must be operated with a differential in order to preventshort cycling. When the supply wate

Page 15 - Heating Curves

4DHW Priority OverrideThere is always the possibility of an excessively long DHW call for heat due to a brokenpipe, faulty aquastat or other problems.

Page 16 - Testing the Control

5In order to overcome this offset, integral control logic is used. Only digital controls can provide integral control logic due to the lengthyresponse

Page 17 - Manual Test

6Optimum Start / Stop with only Indoor Sensors When only indoor temperature feedback is available, the control must base all Opti

Page 18 - Sensor and Internal Faults

7MIXING OPERATION The 371 can supply a lower water temperature to part of the heatingsystem by varying the speed of an injection pump or modulating a

Page 19 - Error Messages

8PID Zone Temperature Control The 371 operation is based on a 15 minute cycle. During every cyclethe control turns on each zone relay for

Page 20 - Technical Data

9UNOCCUPIED (NIGHT SETBACK) The 371 can be switched into UnOccupied mode through the built-in 24 hr. Timer or byclosing an external switch or timer re

Comments to this Manuals

No comments